The INFC
Series combines the features of a controller, monitor and temperature
limit alarm into one easy-to-use digital meter for applications that
require maximum versatility. The INFCT / INFCTP is selectable for J,
K, T, or J DIN thermocouple input with a resolution of 0.1 or 1.0░.
Relay models offer the choice of linear or proportional analog output.
SPECIFICATIONS Input: Thermocouples types, J, K, T, and J DIN Outputs: 2 Form C (SPDT) relays, rated 5 Amp 250 Vac; programmable for active high/low alarms with latching/non-latching relays. The INFCTP includes an NPN open-collector transistor output for time proportional setpoint 1. Relay Hysteresis: programmable from 0 to 9999. Accuracy: ▒0.50░C after 30 min. warm-up Temperature Coefficient: ▒50 PPM/░C Read Rate: 3/sec Step Response: 2 seconds Power: 115 Vac, 230 Vac, 10-32 Vdc, 26-56 Vdc; 6 Watts; 240 V RMS overvoltage protection Isolation: 1500 V peak per Hv test; 354 V peak per IEC spacing NMR: 60 dB CMR: 120 dB Input Resistance: 100 Mohms Operating Temperature: 0 to 50░C Storage Temperature: -40 to 85░C Analog Output: Scalable 0-10 Vdc or 4-20 mA; optional Dimensions: 48 H x 96 W x 152 D mm (1.89" x 3.78" x 6.0") Panel Cutout: 45 x 92 W mm (1.772" x 3.622")
To Order (Specify Model No.) Prices Shown in U.S. Dollars
å Specify order code from Power and Display Codes chart. Ordering Example: INFCT-011, thermocouple thermometer with optional dual relays and analog output, 115 Vac power, red LED display, $395. |